Bryant OM11 19 Manual Pengguna

user’s information manual  
581B  
SINGLE PACKAGE ROOFTOP  
GAS HEATING/  
DuraPac Plus Series  
Sizes 036-150  
1
ELECTRIC COOLING UNITS  
3 to 12 /2 Tons  
Cancels: OM11-19  
OM11-22  
3/15/02  
TO LIGHT UNIT  
NOTE TO INSTALLER:  
WARNING:  
This manual should be left with the equipment owner.  
1. Do not attempt to light by hand; personal injury  
may result.  
2. Before attempting to start the gas heating sec-  
tion, familiarize yourself with all the proce-  
dures that must be followed.  
WARNING: If the information in this manual  
is not followed exactly, a fire or explosion  
may result causing property damage, per-  
sonal injury or loss of life.  
If you do not follow these instructions exactly, a fire or  
explosion may result. Property damage, injury, or loss  
of life could occur.  
— Do not store or use gasoline or other  
flammable vapors and liquids in the  
vicinity of this or any other appliance.  
See Fig. 1 for location of gas valve. Refer to Fig. 2 while  
proceeding through the following steps.  
I. Step 1  
— WHAT TO DO IF YOU SMELL GAS  
• Do not try to light any appliance.  
Set room thermostat to the lowest temperature setting and  
set SYSTEM switch to HEAT or AUTO. position.  
II. Step 2  
Close the manual gas valve.  
• Do not touch any electrical switch; do  
not use any phone in your building.  
• Immediately call your gas supplier from a  
neighbor’s phone. Follow the gas sup-  
plier’s instructions.  
III. Step 3  
Turn off the electrical supply to the unit and install lockout  
tag.  
• If you cannot reach your gas supplier,  
call the fire department.  
IV. Step 4  
Remove the burner access panel.  
— Installation and service must be performed  
by a qualified installer, service agency or  
the gas supplier.  
V. Step 5  
Move the control on the gas valve to the OFF position and  
wait 5 minutes.  
VI. Step 6  
Move control on gas valve to ON position.  
WARNING: Improper installation, adjustment,  
alteration, service, or maintenance could cause prop-  
erty damage, serious injury or death. Refer to this  
manual. For assistance or additional information,  
consult a qualified installer, service agency, or the  
gas supplier.  
WARNING: Before  
performing  
recommended  
maintenance, be sure main power switch to unit is  
turned off. Electrical shock could cause serious injury  
or death.  
Your rooftop combination heating/cooling unit is equipped  
with an automatic direct-spark ignition and induced-draft  
combustion blower.  
WARNING: Do not attempt to light by hand; seri-  
ous injury or death may result.  
Fig. 1 — Typical Gas Valve Location  
(581B090 Shown)  
VII. Step 7  
Replace the burner access panel.  
Should overheating occur, or the gas supply fail to shut off,  
shut off the manual gas valve to the unit before shutting off  
the electrical supply.  
VIII. Step 8  
Turn on the electrical supply to unit.  
Do not use this unit if any part has been under water. Imme-  
diately call a qualified service technician to inspect the unit  
and to replace any part of the control system and any gas  
control which has been under water.  
IX. Step 9  
Open the manual gas valve.  
MAINTAINING YOUR UNIT  
X. Step 10  
All maintenance should be handled by skilled, experienced  
personnel. Your dealer can help you establish a standard  
procedure.  
Set room thermostat selector slightly above room tempera-  
ture to start unit. The induced-draft combustion air fan will  
start. Main gas valve will open and main burners should  
ignite within 5 seconds. If the burners do not light, there is a  
22-second delay before another 5-second try. If the burner  
still does not light, the time delay is repeated. If the burner  
does not light within 15 minutes, there is a lockout. If burn-  
ers still do not light, call for service.  
For your safety, keep the unit area clear and free of combus-  
tible materials, gasoline, and other flammable liquids and  
vapors.  
To ensure proper functioning of the unit, flow of combustion  
and ventilating air must not be prevented from reaching the  
unit.  
WARNING: If the main burners fail to light, or the  
blower fails to start, shut down gas heating section and  
call your dealer for service. Failure to follow these  
requirements could result in serious injury or death.  
To ensure proper airflow, clearance to the condenser coil  
should be 36 in. on one side and 12 in. on the other. Either  
side may receive the greater clearance. A clearance of 1 in.  
from the bottom of the unit to combustible surfaces must be  
maintained when not using a roof curb. A clearance of 0 in.  
from the bottom of the base rail to combustible surfaces must  
be maintained when not using a roof curb. A 60-in. clearance  
above the unit must be allowed for proper condenser fan  
operation.  
XI. Step 11  
Set the temperature selector on the room thermostat to de-  
sired setting.  
TO SHUT UNIT OFF  
A clearance of 42 in. should be allowed on the unit control  
box side. When ungrounded surfaces are present, allow a  
36-in. clearance between unit and the ungrounded surfaces.  
Allow 42 in. between the unit and block or concrete walls or  
other grounded surfaces.  
WARNING:  
1. Do not turn off the electrical power to unit with-  
out first turning off the gas supply.  
2. Never attempt to manually light the main  
burners on unit with a match, lighter, or any  
other flame. If the electric sparking device fails  
to light the main burners, refer to the following  
shutdown procedures. Call your dealer as soon  
as possible.  
Clearance of 48 in. must be maintained between flue side  
and combustible surfaces.  
ROUTINE MAINTENANCE AND CARE  
FOR THE EQUIPMENT OWNER  
Consider the following information before maintaining or  
servicing equipment:  
Failure to follow these procedures could result in seri-  
ous fire or serious injury or death.  
WARNING:  
Refer to Fig. 3 while proceeding with the following steps:  
1. TURN OFF GAS SUPPLY AND THEN ELEC-  
TRICAL POWER TO YOUR UNIT BEFORE  
SERVICING OR PERFORMING MAINTE-  
NANCE.  
I. Step 1  
Set room thermostat to lowest temperature setting and set  
SYSTEM switch to OFF position.  
2. DO NOT turn off electrical power to this unit  
without first turning off the gas supply.  
II. Step 2  
Close the external manual gas valve.  
3. When removing access panels or performing  
maintenance functions inside your unit, be  
aware of sharp sheet metal parts and screws.  
Although special care has been taken to reduce  
sharp edges to a minimum, be extremely care-  
ful when handling parts or reaching into the  
unit.  
III. Step 3  
Turn off the electrical power supply to unit and install lock-  
out tag.  
IV. Step 4  
Remove the burner access panel.  
V. Step 5  
Failure to follow these instructions could result in seri-  
ous fire or serious injury or death.  
Move the control on the gas valve to the OFF position.  
VI. Step 6  
Replace the burner access panel.  
I. AIR FILTERS  
Air filter(s) should be checked at least every 3 or 4 weeks and  
changed or cleaned when necessary. Table 1 indicates the  
correct filter size for your unit. See Fig. 4 for filter access  
door location.  
VII. Step 7  
If unit is being shut down because of a malfunction, call your  
dealer as soon as possible.  
If unit is being shut down because the heating season has  
ended, restore electrical power to the unit to ensure opera-  
tion of the cooling system during the cooling season.  
3—  
MAIN  
ON  
OFF  
LOCK-OUT  
G
TA  
STEP 2  
STEP 3  
STEP 1  
TWO-STAGE GAS VALVE  
SINGLE-STAGE VALVE  
W R  
California Compliant 3-Phase  
581B036-060071  
581B036-060114  
581B048,060149  
Single Phase  
581B036-060072  
581B036-060115  
581B048,060150  
Low NOx  
3-Phase Models  
581B036-072072  
581B036-072115  
581B048-072150  
581B090-102125  
581B090-120180  
581B090-150224  
581B120-150250  
STEP 4  
581B036-060060N  
581B036-060090N  
581B048,060120N  
STEP 5  
STEP 6  
STEP 7  
Fig. 3 — To Shut Unit Off  
4—  
person before each heating season and cleaned when neces-  
sary. This checkout should not be attempted by anyone who  
does not have the required licensing, expertise and/or equip-  
ment to do the job properly. Checking and/or cleaning the heat  
exchanger involves removing the gas controls assembly and  
the flue collector box cover. When finished, the gas controls  
assembly must be reinstalled for proper operation. Also, the  
flue collector box cover must be replaced correctly so that a  
proper seal is maintained. Contact your dealer for the  
required periodic maintenance.  
III. FANS, BELTS, AND FAN MOTOR  
At the beginning of each heating and cooling season, check the  
condition of fan wheels and housings, belt tension, and fan  
motor shaft bearings. No lubrication of condenser or evapora-  
tor fan bearings or motors is required or recommended.  
FILTER ACCESS PANEL  
Fig. 4 — Typical Filter Access Panel Location  
(581B090 Shown)  
IV. EVAPORATOR AND CONDENSER COILS  
Inspect and clean the condenser and evaporator coils at the  
beginning of each cooling season, or more frequently as con-  
ditions require.  
To replace or inspect filters:  
1. Lift up and remove filter access panel.  
2. While holding filter, tilt upper filter track.  
Cleaning of the coils should only be done by qualified service  
personnel. Contact your dealer for the required annual  
maintenance.  
3. Remove filters by pulling up and out toward you from  
the track.  
V. CONDENSATE DRAIN  
4. Inspect or replace filters.  
The drain pan, condensate trap, and drain line should be  
checked and cleaned at the same time the cooling coils are  
checked by your dealer.  
5. Place filters back in the filter tracks. When installing  
filters, note the direction of airflow arrows on the fil-  
ter frame.  
VI. COMPRESSOR  
6. Reinstall filter access panel.  
All compressors are factory-supplied with a normal charge of  
the correct type of refrigeration-grade oil and should not re-  
quire additional oil.  
If you have difficulty locating your air filter or if you have  
questions concerning proper filter maintenance, contact your  
dealer for additional instructions. When replacing your  
units filters, always use the same size and type of filter that  
was originally supplied by the installer.  
VII. CONDENSER FAN  
Units with outdoor air capability have a cleanable filter for  
the outdoor air. This filter should be checked annually and  
cleaned as necessary with steam or hot water and a mild  
detergent. Do not use throwaway filters in place of cleanable  
filters.  
WARNING: Do not poke sticks, screwdrivers, or  
any other object into revolving fan blades. Severe  
bodily injury could result.  
The fan must be kept free of all obstructions to ensure proper  
cooling. Contact your dealer for any required service.  
WARNING: Never operate your unit without fil-  
ters in place. Failure to heed this warning may result  
in damage to the blower motor and/or compressor. An  
accumulation of dust and lint on internal parts of your  
unit can cause loss of efficiency and, in some cases, fire  
that could result in serious injury or death.  
VIII. ELECTRICAL CONTROLS AND WIRING  
Electrical controls are difficult to check without proper  
instrumentation. If there are any discrepancies in the oper-  
ating cycle, contact your dealer and request service.  
IX. REFRIGERANT CIRCUIT  
The refrigerant circuit is difficult to check for leaks without  
the proper equipment. If inadequate cooling is suspected,  
contact your dealer for service.  
Table 1 — Indoor-Air Filter Data  
INDOOR AIR FILTERS  
UNIT SIZE  
(Throwaway Fiberglass)  
581B  
X. COMBUSTION AREA AND VENT SYSTEM  
Quantity  
Size (in.)  
16 x 25 x 2  
16 x 20 x 2  
20 x 20 x 2  
2
4
4
036-072  
090,102  
120,150  
The combustion area and vent system should be visually  
inspected before each heating season. The normal accumula-  
tion of dirt, soot, rust, and scale can result in loss of effi-  
ciency and improper performance if allowed to build up.  
See unit Installation Instructions if optional filters are used.  
When replacing filters, always use the same type and size originally  
supplied.  
NOTE:  
CAUTION: If your unit makes unusual or espe-  
cially loud noises during heating, shut down the heat-  
ing section and call your qualified Bryant dealer.  
II. HEAT EXCHANGER  
To ensure dependable and efficient heating operation, the  
heat exchanger should be checked by a qualified maintenance  
5—  
See Fig. 1 and 5 and proceed as follows to inspect the  
combustion area and venting system of your unit.  
XI. UNIT PANELS  
After performing any maintenance or service on the unit, be  
sure all panels are securely fastened in place to prevent rain  
from entering unit cabinet and to prevent disruption of the  
correct unit airflow pattern.  
1. Turn off gas supply to your unit.  
2. Turn off electrical power to your unit. Install lockout  
tag on disconnect.  
3. Remove compressor and burner access panels.  
REGULAR DEALER MAINTENANCE  
4. Using a flashlight, carefully inspect the burner areas  
for dirt, soot, rust, or scale.  
In addition to the type of routine maintenance you might be  
willing to perform, your unit should be inspected regularly  
by a properly trained and qualified service technician. An  
inspection (preferably each year, but at least every other  
year) should include the following:  
CAUTION: If dirt, soot, rust, or scale accumula-  
tions are found, call your dealer and do not operate  
your heating section.  
1. Inspection of all flue product passages — including  
the burners, heat exchanger, and flue collector box.  
2. Inspection of all combustion- and ventilation-air pas-  
sages and openings.  
5. When you have completed your inspection, follow the  
start-up procedures in this manual to restore your  
unit to operation.  
3. Close inspection of all gas pipes leading to and inside  
your unit.  
6. Observe unit heating operation.  
4. Inspection, and if required, cleaning of the condenser  
and evaporator coils.  
WARNING: Components in heating section may be  
hot after unit has been started. When observing flame,  
be careful not to get close to or touch heating compo-  
nents. Serious personal injury could result.  
5. Inspection and, if required, cleaning of the conden-  
sate drain pan and trap.  
6. Inspection and cleaning of blower wheel housing and  
motor.  
Watch the burner flame to see if it is bright blue. If  
you observe a suspected malfunction or that the  
burner flame is not bright blue, call your dealer.  
7. Inspection of all supply- and return-air ducts for leaks,  
obstructions, and insulation integrity. Any problems  
found should be resolved at time of inspection.  
7. Turn off unit gas supply and electrical power.  
8. Replace compressor and burner access panels.  
8. Inspection of the unit base for cracks, gaps, etc.,  
which may cause a hazardous condition.  
9. Inspection of the unit casing for signs of deterioration.  
10. Inspection of all electrical wiring and components to  
ensure proper connection.  
11. Inspection for leaks in the refrigerant circuit. Pressure-  
check to determine appropriate refrigerant charge.  
12. Inspection and cleaning of fan wheels and housings,  
belt tension, and fan motor and shaft bearings.  
13. Operational check of the unit to determine working  
conditions. Repair or adjustment should be made at  
the time of inspection.  
Your servicing dealer may offer an economical service  
contract that covers seasonal inspections. Ask for fur-  
ther details.  
Complete service instructions can be found in the base unit  
Installation, Start-Up and Service Instructions.  
Fig. 5 — Typical Heat Section Detail  
6—  
BEFORE YOU CALL FOR SERVICE, CHECK FOR  
SEVERAL PROBLEMS THAT CAN BE EASILY SOLVED  
power supply to the unit. Remove the compressor access  
panel.  
If insufficient heating or cooling is suspected:  
(
) During the heating season, check the control switch on  
the gas valve. Is it in the ON position? If it is not, be sure it  
has not been turned off as a safety precaution. If no safety  
hazards are present, follow the start-up procedures in this  
manual.  
(
) Check for sufficient airflow. Check the air filter for dirt.  
Check for blocked return- or supply-air grilles. Be sure they  
are open and unobstructed. If these checks do not reveal the  
cause, call your servicing dealer.  
(
) If your unit still fails to operate, call your servicing  
If your unit is not operating at all, check the following list for  
easy solutions:  
dealer for troubleshooting and repairs. Specify the model  
and serial numbers of your unit. (Record them in this man-  
ual in the space provided.) If the dealer knows exactly which  
unit you have, he may be able to offer suggestions over the  
phone, or save valuable time through knowledgeable prepa-  
ration for the service call.  
(
) Check to be sure that your thermostat temperature se-  
lector is set above the indoor temperature during the heating  
season, or below the indoor temperature during the cooling  
season. Be sure the SYSTEM switch is in the proper HEAT,  
COOL, or AUTO. position and not in the OFF position.  
IN CASE OF TROUBLE  
(
) Is the electrical supply switch ON? Are any fuses blown  
or has the circuit breaker tripped?  
) During the heating season, check the external manual  
If after performing the above routine checks, unit perfor-  
mance is unsatisfactory, shut off the unit and call your  
dealer.  
(
shutoff valve. Is this lever parallel with the pipe, indicating  
that the valve is open? Or is the lever at a right angle, indi-  
cating that the valve is closed? If closed, has the gas been shut  
off for safety reasons? Otherwise, you may open the valve and  
follow the start-up procedures listed in this manual.  
Dealers Name _________________________________________  
Telephone _____________________________________________  
Unit Model ____________________________________________  
Unit Serial Number ____________________________________  
NOTE: Before proceeding with the next check, shut OFF the  
gas supply to the unit and then turn OFF the electrical  
7—  
Bryant Heating & Cooling Systems  
FOR SERVICE OR REPAIR, FOLLOW THESE STEPS IN ORDER:  
FIRST: Contact the installer. You may find his name on the product or in your  
Homeowner's Packet. If the installer’s name is not known, call your builder if  
yours is a new residence.  
SECOND:  
THIRD: Contact:  
Contact the nearest distributor. (See telephone yellow pages.)  
BRYANT HEATING & COOLING SYSTEMS  
Consumer Relations Department  
P.O. Box 4808  
Syracuse, New York 13221  
Phone: 1-800-428-4326  
Model No.  
Unit Serial No.  
Installed by  
Date of Installation  
Name of Owner  
Address of Installation  
Outdoor Cooling or Heating-Cooling Product  
(Units Smaller Than 185,000-Btuh Cooling Capacity)  
Limited Warranty  
Bryant Heating & Cooling Systems (here-  
4. All work shall be performed during normal working hours.  
ONE-YEAR LIMITED WARRANTY —  
inafter referred to as “Company”) warrants this product to be free from defects in  
material and workmanship. If a defect is found within one year from date of  
original installation of product (whether or not actual use begins on that date)  
Company will provide a new or remanufactured part, at Company’s sole option,  
to replace any defective part, without charge for the part itself.  
ALL IMPLIED WARRANTIES (INCLUDING  
LIMITATION OF WARRANTIES —  
IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PAR-  
TICULAR PURPOSE) ARE HEREBY LIMITED IN DURATION TO ONE YEAR.  
SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED  
WARRANTY LASTS, SO THE ABOVE MAY NOT APPLY TO YOU. THE  
EXPRESS WARRANTIES ARE EXCLUSIVE AND MAY NOT BE ALTERED,  
ENLARGED, OR CHANGED BY ANY DISTRIBUTOR, DEALER, OR OTHER  
PERSON WHATSOEVER.  
If a defect  
TEN-YEAR LIMITED WARRANTY ON HEAT EXCHANGER ONLY —  
is found in the heat exchanger within ten years from the date of original installa-  
tion of product, Company will either provide a new or remanufactured heat  
exchanger, without charge for the part itself, or at Company’s option, allow a  
credit in the amount of the then factory selling price for a new equivalent heat  
exchanger toward the retail purchase price of a new Bryant unit.  
COMPANY WILL NOT BE RESPONSIBLE FOR:  
1. Normal maintenance as outlined in the installation and servicing instructions  
or Owner’s Manual, including filter cleaning and/or replacement and  
lubrication.  
2. Damage or repairs required as a consequence of faulty installation, misappli-  
cation, abuse, improper servicing, unauthorized alteration or improper  
operation.  
If a defect is  
FIVE-YEAR LIMITED WARRANTY ON COMPRESSOR ONLY —  
found in the compressor within five years from the date of original installation of  
product, Company will provide a new or remanufactured compressor, at the  
Company’s sole option, to replace any defective compressor, without charge for  
the part itself.  
3. Failure to start due to voltage conditions, blown fuses, open circuit breakers,  
or damages due to the inadequacy or interruption of electrical service.  
4. Damage as a result of floods, winds, fires, lightning, accidents, corrosive envi-  
ronments or other conditions beyond the control of Company.  
5. Parts not supplied or designated by Company, or damages resulting from their  
use.  
6. Company products installed outside the continental U.S.A., Alaska, Hawaii,  
and Canada.  
7. Electricity or fuel costs, or increases in electricity or fuel costs from any  
reason whatsoever, including additional or unusual use of supplemental elec-  
tric heat.  
FIVE-YEAR LIMITED WARRANTY ON ELECTRICAL ELEMENT FOR AIR  
If a defect is found in any electrical element within five years  
HEATING ONLY —  
from the date of original installation of product, Company will provide a new or  
remanufactured electrical element, at the Company’s sole option, to replace  
defective electrical element, without charge for the part itself.  
None of these warranties include labor or other costs incurred for diagnosing,  
repairing, removing, installing, shipping, servicing or handling of either defective  
parts, or replacement parts, or new units.  
WARRANTY CONDITIONS:  
1. Warranties apply only to products in their original installation location.  
2. Installation, use, care, and maintenance must be normal and in accordance  
with instructions contained in the Owner’s Manual and Company’s service  
information.  
3. Defective parts must be returned to the distributor through a registered servic-  
ing dealer for credit.  
8. ANY SPECIAL INDIRECT OR CONSEQUENTIAL PROPERTY OR COM-  
MERCIAL DAMAGE OF ANY NATURE WHATSOEVER. Some states do not  
allow the exclusion of incidental or consequential damages, so the above  
limitation may not apply to you.  
This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.  
Catalog No. 5358-110  
Effective on product manufactured after July 1, 1987. Supersedes any other warranty certificates supplied with the product.  
39004DP247  
Copyright 2002 Bryant Heating and Cooling Systems  
CATALOG NO. 5358-111  

Brother MFC 465CN Manual Pengguna
Brother MFC 760 Manual Pengguna
Brother MFC 5460CN Manual Pengguna
Brother MFC 8860 Manual Pengguna
Century PM 1645AA Manual Pengguna
Charles Bentley Son Solid Power AE Series Manual Pengguna
Friedrich Penyesuai Udara CP06A10 Manual Pengguna
Friedrich Penyesuai Udara SS09 Manual Pengguna
Garmin MC34676B Manual Pengguna
Honeywell Pembaca Barkod 3800 Manual Pengguna